EmissionsTier 4 Final EPA-Certified for Nonroad Applications
Sound Levels68 dB(A) log average @ 7 m (23 ft.) with full load at the prime rating
Fuel Capacity/Run Time63 gal.
Standard Features
One-source responsibility for the generating system and accessories.
Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
Approved for use with certified renewable Hydrotreated Vegetable Oil (HVO)/Renewable Diesel (RD) fuels compliant with EN15940/ASTM D975.
The generator set and its components are prototype-tested, factory-built, and production-tested.
A three-year, 3000-hour limited warranty covers all generator set systems and components. The trailer has a one-year limited warranty.
Unit-mounted radiator with 45˚C (113˚F) ambient air capability at the prime rating.
NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
Capable of sustained line-to-neutral short-circuit current of up to 300% of the rated current for up to 2 seconds. (IEC 60092-301 short-circuit performance.)
Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
Windings are vacuum-impregnated with polyester resin for dependability and long life.
Standard Features
One-source responsibility for the generating system and accessories.
Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
Approved for use with certified renewable Hydrotreated Vegetable Oil (HVO)/Renewable Diesel (RD) fuels compliant with EN15940/ASTM D975.
The generator set and its components are prototype-tested, factory-built, and production-tested.
A three-year, 3000-hour limited warranty covers all generator set systems and components. The trailer has a one-year limited warranty.
Unit-mounted radiator with 45˚C (113˚F) ambient air capability at the prime rating.
NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
Capable of sustained line-to-neutral short-circuit current of up to 300% of the rated current for up to 2 seconds. (IEC 60092-301 short-circuit performance.)
Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
Windings are vacuum-impregnated with polyester resin for dependability and long life.
Engine Features
Heavy-duty air cleaner with electronic air restrictor indicator switch.
The generator set engine is certified by the Environmental Protection Agency (EPA) to conform to Tier 4 Final nonroad emissions regulations.
Uses cooled Exhaust Gas Regeneration (EGR) and Diesel Oxidation Catalyst (DOC) to meet Tier 4 Final without a Diesel Particulate Filter (DPF).
Battery disconnect switch.
Enclosure/tank Features
Durable steel, sound-attenuating housing with quiet operation of 68 dB(A) log average @ 7 m (23 ft.) with full load at the prime rating.
Stainless steel hinges and lockable latches on doors.
100% secondary containment tank for fuel.
Single-point lifting eye and four-point tie down system.
Subbase fuel tank for 25-hour run time with full load at prime rating (minimum).
Customer Connection Panel Features
Decision-Maker® 3500 controller with potted circuitry for protection from vibration and debris.